|
|
Design Philosophy for Transformer PitIn
this page I will talk about how to detemine the size of oil containment
for transformer. Following is a typical picture of a transformer and
its foundation with oil containment. ![]() Now, you will follow the below steps to determine the foundation and size of spilled oil containment. Step-1 : Review of Transformer drawing (Vendor Equipment Drawing)
You need to review Plot plan, Equipment location drawings and 3 -D Models and check whether you have all the following information:
Following Geotechnical information are required to start the foundation and spilled oil containment:
Transformer pedestal shall be sized according to the following criteria: Face-to-face pedestal size shall be the larger of the following: (a) Bolt c/c distance + 175mm (b) Bolt c/c distance + 8 x bolt diameters (c) Bolt c/c distance + sleeve diameter + 150mm (d) Size of base frame + 200mm (e) Bolt c/c distance + 2 x (minimum bolt edge distance) Step-5 : Transformer spilled oil containment sizing criteria: Containment size shall be calculated for worst condition. It is assumed that worst condition will be happened when total oil is in the containment + Transformer on fire + Heavy rain fall. So, total containment volume will be, addition of following items:
Step-6 : Anchor Bolt Check: Design of anchor bolts shall be based on the following considerations. Corrosion allowance should be considered when required by the project design criteria. Tension Check: The maximum tension force in the anchor bolts (Tmax) may be calculated according with following formula: Tmax = M / (Ny x BCD) - (De / Do) / Nb Where, M = total maximum moment on foundation BCD = Bolt c/c distance Ny = No. of bolt row Nb = no. of anchor bolt Use De or Do whichever is critical. Shear Check: When anchor bolts are utilized to resist shear, the unit shear per bolt shall be calculated as follows: Vmax = V / Nb where, V = total shear force on anchor bolt. Frictional resistance to shear between the transformer base plate and the concrete or grouted bearing surface shall be utilized to resist shears induced by wind or by other static loads. Frictional resistance shall not be employed to resist shear induced by seismic loads. For seismic-induced shear, adequate mechanical means shall be provided to resist horizontal shear, either by means of properly detailed anchor bolt / bolt hole arrangements or through a combination of anchor bolts, shear lugs, or other anchorage devices. The static coefficient of friction between steel and concrete or between steel and cementitious grout shall be considered as 0.4 or specified in project design criteria. Tension Shear Interaction check: When anchor bolts are subjected to combined shear and tension loads, the design shall be based on satisfying interaction formula (say Appendix-d of ACI 318). Please note that anchor bolt edge distance, spacing and load capacity shall be as per project design criteria. Step-7 : Load combinations for foundation sizing / Pile loads and Foundation design: You need to create the load combination per your project design criteria. However, I have created this load combination based on ACI 318: Load combination for Foundation sizing and Pile load calculation (un-factored load calculation):
Step-8 : Loads on containment wall Containment wall shall be designed for following loads and load combinations:
For requirement of firewall refer NFPA-850 chapter-5. Now from above steps, you have learnt the following:
Question from visitor: Do I need to consider soil passive pressure on transformer wall for sliding check, when the transformer pit is in high seismic zone? Recommendation from Subhro: It is advisable not to consider any passive pressure on wall for sliding check, when pit is in high seismic zone. If it is absolute necessary to consider the passive pressure on wall for sliding check, you must consult with geotechnical engineer for recommendations. Recommendations courtsey: Soumyabrata Roychowdhury, Civil/Structural Engineer I hope this page will be very helpful to you to understand the basic loads for transformer foundation and containment pit design Copyright 2009. All rights reserved. Please do not print or copy of this page or any part of this page without written permission from Subhro Roy. Disclaimer: This page is prepared based on experience on Civil Engineering Design. All definitions and most of the explanations are taken from different text books and international design codes, which are referenced in the contents. Any similarity of the content or part of with any company document is simply a coincidence. Subhro Roy is not responsible for that. |